Battery Runtime Calculator
Runtime straight from a battery's watt-hours - for laptop batteries and anything else labelled in energy.
Roughly how long a UPS keeps a load running, from its battery rating and what you have plugged into it.
7 inputs · Free, no sign-up ·
Estimates only. Rates, fees and specifications change. Confirm against the official source before you rely on a figure — see our disclaimer.
A desktop UPS gives you minutes, not hours, and that is the point of it. It exists so you can save your work and shut down cleanly, not so you can keep working through a power cut.
A typical small UPS with a 12 V 7.2 Ah battery holds about 86 Wh. Running a 150 W desktop and monitor, that is around twenty-eight minutes at 80% efficiency — and rather less in practice, because the battery is probably not new.
Battery energy = Voltage x Capacity
Usable energy = Battery energy x Efficiency
Backup time = Usable energy / Load
The efficiency covers the inverter's conversion loss. It does not cover the fact that a sealed lead-acid battery discharged hard delivers well below its rated capacity — a battery rated over 20 hours being emptied in 20 minutes gives substantially less than the label. That is why the real figure tends to fall short of this one.
| Symbol | Meaning | Unit |
|---|---|---|
| V | UPS battery voltage | V |
| Ah | UPS battery capacity | Ah |
| Load | Total connected load | W |
| Efficiency | Inverter efficiency | % |
A 12 V 7.2 Ah UPS battery running a 150 W desktop at 80%:
Energy = 12 x 7.2 = 86.4 Wh
Usable = 86.4 x 0.80 = 69.1 Wh
Backup = 69.1 / 150 = 0.46 h = about 28 minutes
Halve the load and you roughly double the time, which is why unplugging the monitor during a cut buys you noticeably longer.
For a typical desktop UPS with a 12 V 7.2 Ah battery and a 150 W load, roughly 20 to 30 minutes when new - and less as the battery ages. UPS units are designed for a clean shutdown rather than for working through an outage.
Battery age, almost always. Sealed lead-acid batteries lose capacity steadily and are usually due for replacement after three to five years, sooner in a hot room.
Some UPS models support external battery packs and are designed for it. Fitting a larger battery to a unit not built for it can overload the charging circuit. Check the manufacturer's documentation rather than assuming.
No. A laser printer's warm-up draw is very large and will trip or flatten a typical desktop UPS. Plug it into a surge-protected socket that is not battery-backed.
Runtime straight from a battery's watt-hours - for laptop batteries and anything else labelled in energy.
How long a home inverter runs your load, with the lead-acid depth of discharge that decides the real answer.
How long a battery of a given voltage and capacity runs a given load, with the conversion loss shown rather than hidden.
What a particular load does to a particular battery - how long it runs and how much energy it takes.
How long a power bank runs a device, and how many charges it gives a phone whose battery you supply.
How long a battery takes to charge, with the slowdown above 80% accounted for instead of ignored.