UPS Backup Calculator
Roughly how long a UPS keeps a load running, from its battery rating and what you have plugged into it.
How long a home inverter runs your load, with the lead-acid depth of discharge that decides the real answer.
7 inputs · Free, no sign-up ·
Estimates only. Rates, fees and specifications change. Confirm against the official source before you rely on a figure — see our disclaimer.
The figure that decides inverter backup is not the battery rating — it is how much of the battery you are willing to use. A 150 Ah lead-acid battery holds 1,800 Wh, but discharging one below about half repeatedly shortens its life sharply, so the practical energy is closer to 900 Wh before the inverter's own losses.
That single fact halves most people's expectations, and it is why an inverter that "should" run four hours runs two.
Battery energy = Voltage x Capacity
Usable energy = Battery energy x Efficiency
Backup time = Usable energy / Load
Two separate reductions are at work and this page lets you combine them in one figure. The inverter converts DC to AC and loses 15–20% doing it. Separately, a lead-acid battery should not be taken below roughly half its capacity. Multiply the two and you get around 40–45%, which is why that is the efficiency to use for a realistic answer.
Lithium batteries change this materially: they tolerate much deeper discharge, so their usable share is far closer to the nominal figure.
| Symbol | Meaning | Unit |
|---|---|---|
| V | Battery bank voltage | V |
| Ah | Battery capacity | Ah |
| Load | Total household load | W |
| Efficiency | Inverter, and usable depth | % |
A 12 V 150 Ah battery running a 300 W household load:
Energy = 12 x 150 = 1,800 Wh
At 80% - inverter only:
Usable = 1,440 Wh -> 4.8 hours
At 45% - inverter plus half-discharge limit:
Usable = 810 Wh -> 2.7 hours
The second is the number to plan around with a lead-acid battery.
With a 300 W load, about 2.7 hours realistically - using 45% to cover both the inverter's losses and not discharging a lead-acid battery past half. The optimistic figure ignoring depth of discharge is nearer 4.8 hours, and planning on it will shorten the battery's life.
Usually because their figure ignored depth of discharge, or assumed a lighter load than you actually run. Battery age and a heavy discharge rate both reduce it further.
The inverter alone is around 80-85%. For a realistic lead-acid answer use 40-45%, which combines that with only using half the battery. For lithium, 80% is closer to right because deep discharge is acceptable.
Either adds capacity. Two batteries in series double the voltage and let the same power flow at half the current, which means less loss in the cabling; two in parallel keep the voltage and double the amp-hours. Your inverter dictates which it supports.
Roughly how long a UPS keeps a load running, from its battery rating and what you have plugged into it.
What a particular load does to a particular battery - how long it runs and how much energy it takes.
Runtime straight from a battery's watt-hours - for laptop batteries and anything else labelled in energy.
How long a battery takes to charge, with the slowdown above 80% accounted for instead of ignored.
How long a battery of a given voltage and capacity runs a given load, with the conversion loss shown rather than hidden.
How full a battery is as a percentage, from the charge left in it or the charge taken out.